ZLCD***1 zinc oxide arrester with electric testing instrument is
dedicated and used to verify electric performance of zinc oxide
arrester,it is suitable for all kinds of voltage level zinc oxide
arrester with and without electric testing, thus detect moisture
inside the device and valve insulation aging and other dangerous
defects.
Instrument is easy to operate and use,microcomputer control the
whole process,can measure zinc oxide arresters full
currentã€resistive current and its harmonic waveã€power frequency
reference voltage and harmonic waveã€active power and phase
difference, big screen can display real waveform of voltage and
current. Instrument is using digital wave analysis
technology,adopts harmonic analysis and digital filtering and so
on software resisting interference method which makes testing
result to be accurateã€stable,can analyze accurately fundamental
wave and 3 ~7 harmonic content,and can overcome the impact of
interference between phases, correctively measure resistive current
of side phase arrester.
Features:
I. **0×**0 color LCD touch
panel, high speed thermal printer; photo and context display and
intuitive interface, it is easy for onsite operation and use.
II. Wireless transmission PT
signal is over **0 meters,if special requirement configuration,
can up to ***0 meters.
III. It is suitable and used for arrester
with powerã€no power and lab room and so on please.
IV. Really do 3 phases current and 3
phases voltage testing at the same time, improve working
efficiency; Instrument only bring weak power internally, voltage
is no more than *2V; Currentã€voltage sensor is totally
quarantined,safe and firmly.
V. Supports both wire
synchronizationã€wireless sync voltage reference signal
samplingï¼›also supports no voltage method, find voltage
reference by software calculation.
VI. Select equipped high power lithium
ion battery, very helpful for no power place. Instrument only
have weak electric.
VII.Equipped with embedded industrial grade operating
system, support direct shut down method; equipped one USB port,
support U disk export data; can plug external USB
mouseã€keyboard , easy operation.
VIII. Internal equipped 4G capacity SD
card can store big volume data, and have data
managementã€storage function and so on.
IX. Equipped superior management
software,have historical data managementã€data
analysisã€report printing function and so on.
X. High speed sampling
frequency,advanced digital signal process technology,strong
anti-interference ability, super high accuracy of testing result.
XI. Adopt
dust-proofã€water-proofã€anticorrosion engineering plastic
sealed box,small size,light weight,easy for hand carry.
Parameters:
I. Working
power:**0Vã€*0Hz or internal battery for power supply.
II. Measurement scope:
Leakage current ***0mA(scalable),
voltage:*****0V(scalable)
III. Measurement accuracy:
Current:full current >**0μA: ±5%
reading 1 bit,
Voltage:reference voltage signal >*0V: ±5% reading±1 bit.
IV. Measurement parameter:
Leakage current full current wave formã€reference wave valid
valueã€peak value.
Leakage current resistive component reference wave valid value
and 3ã€5ã€7 times valid value.
Leakage current resistive component peak value:positive peak
value Ir+ negative peak value Ir-.
Capacitive current reference wave,full voltageã€full current
and phase angle difference.
Voltage effective value.
Arrester power lost.
V. Voltage reference signal sampling method:
Wire sync:*0 meters(scalable)
Wireless sync:>**0
meters(scalable)
VI. Battery parameters:
Charge
time > 6 hours
Continual working time > 4 hours
Interrupted working time > 8 hours
VII.Instrument dimension: host
*6cm×*6cm×*4cm equipped assessor case *2cm×*3cm×*0cm
VIII. Instrument weight: host 5.0kg, equipped
assessor case: 9.0kg