La description
Applicable Standards
The Quality Management System shall be ISO
***1 Certified. The equipment shall comply with the latest
revision of the following standards:
ANSI/IEEE
C*7.*0IEEE
Standard Requirements for Overhead, Pad-Mounted, Dry-Vault, and
Submersible Automatic Circuit Reclosers and Fault Interrupters
for AC Systems.
IEC
********1High-voltage switchgear and controlgear
Part **1: Automatic circuit reclosers and fault interrupters for
alternating current systems up to *8 kV.
ISO
***1Hot
dip galvanized coatings on fabricated iron and steel articles-
Specifications and test methods.
IEC
********1Classification of environmental conditions
Part **1: Environmental conditions appearing in nature
  Temperature and humidity
IEC ****9
 Degrees
of protection provided by enclosures (IP Code)
IEC
******3Selection and dimensioning of high-voltage
insulators intended for use in polluted conditions - Part 3:
Polymer insulators for a.c. systems.
IEC
****9Composite insulators for a.c. overhead
lines with a nominal voltage greater than ***0 V Definitions,
test methods and acceptance criteria.
IEC
**********4Transmission Protocols, Network access for
IEC **********1 using standard transport
profiles.
IEC ****0
 Sampling plans and procedures for
inspection by attributes
Â
Â
Â
Â
Ratings Â
Voltage Â
Â
Rating
|
CHZ***5
|
CHZ***7
|
CHZ***8
|
Maximum Design Voltage
(kV)
|
*5.5
|
*7.0
|
*8.0
|
Nominal Operating Voltage
(kV)
|
*4.4
|
*4.9
|
*4.5
|
Basic Insulation Level
(kV)
|
**0
|
**5
|
**0
|
Â
Â
Current Â
Â
Rating
|
CHZ***5
|
CHZ***7
|
CHZ***8
|
Continuous Current (A)
|
**0/**0
|
**0/**0
|
**0/**0
|
Symmetric Interrupting Current
(kA)
|
*2,5 - *5
|
*2,5 - *5
|
*2,5 - *5
|
Overload Capability
(A)
|
Â
|
Cable Charging Current
(A)
|
*0
|
*5
|
*0
|
Three-Second Current Symmetric
(kA)
|
*2,5 - *5
|
*2,5 - *5
|
*2,5 - *5
|
Â
Â
Mechanical Lifespan
Â
Â
Rating
|
CHZ***5
|
CHZ***7
|
CHZ***8
|
Minimum Operations
|
*0,**0
|
*0,**0
|
*0,**0
|
Â
Â
Frequency Â
Â
Rating
|
CHZ***5
|
CHZ***7
|
CHZ***8
|
Rated Frequency (Hz)
|
*0/*0
|
*0/*0
|
*0/*0
|
Â
Â
Creepage Â
Â
Rating
|
CHZ***5
|
CHZ***7
|
CHZ*- *8
|
Creepage Distances
|
mm (in)
|
mm (in)
|
mm (in)
|
Terminal to Terminal
|
***2 (*1.5)
|
***2 (*1.5)
|
***2 (*1.5)
|
Lower Terminal to
Ground
|
**3 (*6.5)
|
**0 (*0.0)
|
**0 (*7.5)
|
Â
MAIN BODY CONSTRUCTION
The automatic reclosers are
constructed with vacuum interrupters with magnetic actuation
mechanism, with solid resin insulation.
Coupled three-phase
operation
The reclosers will be
bi-directional therefore suitable for forward and reverse current
flow.
Â
Materials
All materials used in the
manufacture of reclosers shall be highly resistant to the
corrosion of saline atmospheres.
Â
Surface
treatment
The ferrous parts shall be of
stainless steel for enclosures and cabinets. Corrosion treatment
by means of hot dip galvanizing in accordance with ISO ***1 is
only permitted for support structures and fastening
components.
Â
Insulators
The insulators will be of solid
dielectric insulation with the cycloaliphatic epoxy resin system
or silicone rubber type HTV, Porcelain or EPDM insulators are not
allowed.
The creepage distance shall be at
least *1 mm/kV. Insulators shall withstand a bending motion of
**0 Nm and withstand a suitable torque for the fastening of the
conductors.
The insulation material must have
a hydrophobic behavior, highly resistant to ozone, oxygen,
moisture, pollution and ultraviolet (UV) radiation resistant
(according to IEC ****9). No UV coatings or covers are
accepted.
Â
Â
Â
Position
indicators
Position indicators shall be
resistant to aggressive weather conditions, possibly by the
adoption of transparent protection, and shall be of such
dimensions as to be clearly visible from the base of the pole and
in any case at a distance of 8 m.
 CONTROLLER The components of control,
protection and remote control must be located in a box treated
against corrosion.
The box will be designed to
protect electronic circuits from aggressive weather
conditions.
The cabinet will be supplied with
all the appropriate connectors to ensure connection with the
recloser.
The cabinet door must have a
secure locking system with an operating handle that allows
locking. It must provide a lock with a master
key.
Â
General
characteristics
The cabinet shall be IP *5
class;
Access profiling to control should
prevent unauthorized persons from logging in. The access to the
configuration of the control must be protected through a minimum
of two access keys, one of basic operator and one of engineering
or configuration.
A voltage suppressor protection
shall be provided for the AC voltage auxiliary on the low
voltage side of the potential transformer or auxiliary voltage,
suitably sized to protect the control against atmospheric or
system surges.
Â
Power
Supply
The rectifier / back up battery
must have sufficient capacity to supply all the control equipment
as well as the communications equipment. The voltage is in
all cases ******0 VAC, *0/*0 Hz coming from an auxiliary
transformer, or directly from the LV network. All auxiliary parts
will be supplied at  *4 V DC.
The rectifier shall have the
necessary alarms to monitor its correct operation, and the
battery shall have sufficient capacity to maintain the operation
of the system for *4 hours or to perform at least four cycles of
opening / closing operations. The battery shall be included in
the delivery.
The battery charger must have some
visual indication that informs that the battery is discharged, or
has a fault requiring maintenance or change.
Â
Local control and protection
functions
The recloser control will have the
following protection functions:
-Â Phase overcurrent
protection (****1),
-Â Residual overcurrent
protection (*0N**1N),
-Â Directional overcurrent
protection (*7),
-Â Residual directional overcurrent
protection (*7N),
-Â Automatic multiple reclosing
function (*9)
It must have at least two
alternative profiles for the different protection functions
including the possibility to program protection curves. Typically
one of the profiles will be used in case the power flows from the
Source side to the Load side, and the other to the opposite side.
The change from one to another setting will be made automatically
by the equipment upon detecting change in the direction of power
flow or by means of pushs or local switch.
Â
Â
Other local and remote
functions
Activation / deactivation Hot Line
Tag mode with led status indicator (switched on if the function
is active): Prevents switching operation by remote control and
only allows a first protection trip with programmable fast curve,
inhibiting reclosing, both automatic, from panel, by connection
to computer and even from SCADA. It can only be deactivated in
the same way as activated (for example, if activated locally, it
can only be deactivated locally and not by SCADA or computer).
The indicator light will always remain on while the function is
active.
Local indication
of:
-Â Position of
the switch
-Â Automatic
reclosing status
-Â Protection on /
off status
-Â Status on / off Hot
Line Tag
- General Alarms
Â
Ability to store operation events.
The events to register will be at least:
-Â Oscillographic record of events
and stored in Comtrade format
-Â Opening or
closing operation
Pays: |
China |
N ° de modèle: |
CHZ4
|
Prix FOB: |
8000 ~ 1000 / Box (Negotiable)
Obtenir le dernier prix
|
Localité: |
CHINA |
Prix de commande minimale: |
8000 per Box |
Commande minimale: |
1 Box |
Packaging Detail: |
WOODEN |
Heure de livraison: |
45DAYS AFTER ORDER |
Capacité de Fournir: |
10000 Box per Year |
Payment Type: |
D/P, D/A, L/C, T/T |
Groupe de produits : |
33KV-245KV Power Substation
|